Not too long ago, a contractor called and asked us why his new "Brand X" (not
Greenheck) kitchen exhaust hood was sweating. He had purchased a short circuit hood
that brought in untempered make-up air. Here was our response:
Visible condensation will occur when a surface temperature is below the room air dew
point. In this case, when the relative humidity in the kitchen is high enough and the
outside air is cold enough, water droplets will form on the cold metal surface of the
kitchen hood. An example would be:
| Room Temperature |
Percentage of
RH in Kitchen |
Outside Air Temperature
(or Colder) |
| 70º F |
10% |
12º F |
| 70º F |
20% |
28º F |
| 70º F |
30% |
37º F |
| 70º F |
40% |
45º F |
| 70º F |
50% |
59º F |
or, for example, if the relative humidity in the kitchen is 30% and the outside air
temperature is 37º F (or colder), then condensation will occur on the cold surfaces of
the hood.
The solution is either:
- Shut off the make-up air and pull the cold make-up air in the front door, through the
building and across the occupants (similar to what you find in most restaurants) and
finally in to the kitchen area. The air will warm up as it passes over customers, their
food and the employees before it gets to the kitchen . . . . . . , or
- Seal off the "short circuit baffles", cut in supply registers to allow the
make-up air unit to be introduced into the kitchen, and add 80 BTU/hr (23 watts
electrical) per CFM of air being heated, i.e., 80,000 BTU/hr or 23 KW per 1,000 CFM of
outside air.
As you know, animal fat (the vaporous byproduct of frying meat) congeals at room
temperature (70º F) and this process accelerates as the temperature is lowered. When you
"short circuit" cold air directly into the "grease" filters, they
become "lard accumulators". This is one of the benefits of a short circuit hood
--- a built-in lard trap. Because the animal fat congeals on surfaces like filters and
ducts, it does not run down and drain as required in mechanical code books. This
condition is a fire hazard.
Imagine this for a moment - exhaust fan exhausting 3,000 CFM with an outside air
make-up air fan short circuiting 2,500 CFM - this only leaves 500 CFM of exhaust air to
capture cooking vapors rising up from the cooking surfaces.
If all you need to capture from the cooking process is 500 CFM, then scrap the make-up
air unit and slow the exhaust fan down to 500 CFM.
If all you're doing is chopping lettuce and warming potatoes, then 500 CFM is probably
OK; however, if you're preparing meals for several hundred people, an analysis of the
cooking appliances (type and size) will determine the contaminated air quantity rising up
from these surfaces. Refer to Greenheck's design manual for proper air flow design. You
need to be exhausting properly calculated volumes and introducing treated make-up air into
the kitchen area.
Although the BOCA National Mechanical code does not specifically prohibit "short
circuit" hoods, the Commonwealth of Kentucky strongly discourages them and prefers
that they not be installed in Kentucky. The BOCA code does require that:
M-504.5.2 Make-up Air: Make-up air shall be supplied during the operation of the
kitchen exhaust system. The amount of make-up air shall be approximately equal to the
amount of exhaust air. The make-up air shall not reduce the effectiveness of the exhaust
system.
The temperature differential between make-up air and air in the conditioned space shall
not exceed 10º F. (5.5º C.).
Exceptions
- Make-up air that is part of the air conditioning system.
- Make-up air that does not decrease the comfort conditions of the occupied space.
The Indiana Mechanical code states:
". . . . . . Compensating hoods shall extract at least fifty percent (50%) of the
required air flow from the kitchen area."
and that:
". . . . . . The make-up air shall not reduce the temperature of the occupied
space to less than sixty-five degrees Fahrenheit (65º F) at five (5) feet above the floor
throughout the room."
In summary, properly designed kitchen exhaust systems should have the following
elements:
| A. |
Supply and exhaust CFM calculations based on the equipment
under the hood. |
|
|
| B. |
Tempered supply (make-up air) introduced into the room, not
untreated, new air supplied under the hood. |
For additional design/equipment selection information, please contact one of our sales
associates.
Always remember . . . . . . . . .
(1) part empherical formula + (2) parts horse sense =
"good design techniques"
Doc